Grounding Electrode Conductors and a splice.

August 17, 2017 by danmcconnon

Grounding Electrode Conductors and a splice. Wenatchee Home Inspections


In general, the grounding electrodes and their conductors create a connection of the electrical system to the earth (earthing). The earth is considered to be at zero potential. The second function of the system is to dissipate over-voltages into the earth. Overvoltages can come from the system itself or from lightning.



It is typically required that the grounding electrode conductor (GEC) should be one continuous length without a splice. But there there may become a time that it amay require a splice such as when work is done during remodeling or the replacement of existing electrical equipment. Another cause could be copper thieves.  They have been known to cut or remove sections of the grounding electrode conductor. So what is next?

You are not allowed to just splice together as in this example from a home inspection.





The code states (from the 2014/2017 NEC);

250.64

(C) Continuous.

Except as provided in 250.30(A)(5) and (A)(6), 250.30(B)(1), and 250.68(C), grounding electrode conductor(s) shall be installed in one continuous length without a splice or joint. If necessary, splices or connections shall be made as permitted in (1) through (4):

1)Splicing of the wire-type grounding electrode conductor shall be permitted only by irreversible compression-type connectors listed as grounding and bonding equipment or by the exothermic welding process.

2)Sections of busbars shall be permitted to be connected together to form a grounding electrode conductor.

3)Bolted, riveted, or welded connections of structural metal frames of buildings or structures.

4)Threaded, welded, brazed, soldered or bolted-flange connections of metal water piping.

So we have 4 means of creating a splice.


Here is an example of a compression type of connector-

Here are examples of an exothermic weld type of connections, also know as a “Cadweld”

             

Cadweld plus Cadweld-Standard

 

 


“Remember that current always returns to its source through either an intentional or accidental path – electrons don’t care and they don’t read schematics!”

Gerke, D. and Kimmel, W

 


If you find any errors or have additional information that would expand on any code, building standards or manufacturer requirements please let me know.



NCW Home Inspections, LLC  is a Licensed Washington State Home Inspection service located in Wenatchee Washington serving Chelan County, Douglas County, Kittitas County, Okanogan County and Grant County Washington and the cities of Wenatchee, Leavenworth, Cashmere, Oroville, Cle Elum, East Wenatchee, Quincy and many more…  

Your Wenatchee and Chelan Professional Real Estate, Home and Structural Pest Inspection Service

Instructor- Fundamentals of Home Inspection-  Bellingham Technical College

WA Home Inspector Advisory Licensing Board

www.ncwhomeinspections.com                                                   509-670-9572

You can follow me on Facebook, Twitter, Google+ and on my website Blog.

                      



Grounding Electrode Conductors and a splice. Wenatchee Home Inspections


In general, the grounding electrodes and their conductors create a connection of the electrical system to the earth (earthing). The earth is considered to be at zero potential. The second function of the system is to dissipate over-voltages into the earth. Overvoltages can come from the system itself or from lightning.



It is typically required that the grounding electrode conductor (GEC) should be one continuous length without a splice. But there there may become a time that it amay require a splice such as when work is done during remodeling or the replacement of existing electrical equipment. Another cause could be copper thieves.  They have been known to cut or remove sections of the grounding electrode conductor. So what is next?

You are not allowed to just splice together as in this example from a home inspection.





The code states (from the 2014/2017 NEC);

250.64

(C) Continuous.

Except as provided in 250.30(A)(5) and (A)(6), 250.30(B)(1), and 250.68(C), grounding electrode conductor(s) shall be installed in one continuous length without a splice or joint. If necessary, splices or connections shall be made as permitted in (1) through (4):

1)Splicing of the wire-type grounding electrode conductor shall be permitted only by irreversible compression-type connectors listed as grounding and bonding equipment or by the exothermic welding process.

2)Sections of busbars shall be permitted to be connected together to form a grounding electrode conductor.

3)Bolted, riveted, or welded connections of structural metal frames of buildings or structures.

4)Threaded, welded, brazed, soldered or bolted-flange connections of metal water piping.

So we have 4 means of creating a splice.


Here is an example of a compression type of connector-

Here are examples of an exothermic weld type of connections, also know as a “Cadweld”

             

Cadweld plus Cadweld-Standard

 

 


“Remember that current always returns to its source through either an intentional or accidental path – electrons don’t care and they don’t read schematics!”

Gerke, D. and Kimmel, W

 


If you find any errors or have additional information that would expand on any code, building standards or manufacturer requirements please let me know.



NCW Home Inspections, LLC  is a Licensed Washington State Home Inspection service located in Wenatchee Washington serving Chelan County, Douglas County, Kittitas County, Okanogan County and Grant County Washington and the cities of Wenatchee, Leavenworth, Cashmere, Oroville, Cle Elum, East Wenatchee, Quincy and many more…  

Your Wenatchee and Chelan Professional Real Estate, Home and Structural Pest Inspection Service

Instructor- Fundamentals of Home Inspection-  Bellingham Technical College

WA Home Inspector Advisory Licensing Board

www.ncwhomeinspections.com                                                   509-670-9572

You can follow me on Facebook, Twitter, Google+ and on my website Blog.

                      

Primary Sidebar

  • Menu
  • Gallery
  • Blog

Informational Pages

  • Blog
  • Foundation Certifications
  • Prices
  • Qualifications
  • Services Performed
  • Testimonials
  • Washington State Home Inspector Standards of Practice
  • What’s Inspected and Services
  • Areas Served
  • Credit card
  • City/County/State Building Codes
  • Frequently Asked Questions
  • General Home Information
  • Homeowner Maintenace Guides
  • Infrared Thermography
  • Recall Resources
  • Reference Documents
  • Inspection Agreement and Washington State Standards of Practice
  • Home and Building Inspections Wenatchee, Chelan and Surrounding Areas
    • About Me and Training Information
  • google verify

Copyright © 2025 Administrator. All rights reserved.