• Skip to main content
  • Skip to primary sidebar

Administrator

The Confluence of Quality and Integrity

Coming down the Pike- New AFCI rules for 2014

March 17, 2014 by danmcconnon

Coming down the Pike-  New AFCI rules for 2014

Well there is a buzz  in the electrical world with the upcoming adoption of the 2014 NEC, (on July 1, 2014 for Washington State). The big one is in regards to AFCI (Arc Fault Circuit Interrupter) protection, and now all the areas they are to cover. (Here is an article from 2012 on why AFCI protection-  Link )

                     Arc Fault

But now the debate rages on about the new rules from the 2014 NEC in regards to these devices, their cost versus protection they provide.

2014 NEC article- 210.12Arc-Fault Circuit-Interrupter Protection

Arc-fault circuit-interrupter protection shall be provided as required in 210.12(A) (B), and (C). The arc-fault circuit interrupter shall be installed in a readily accessible location.

                      Arc Fault breaker Circuit

(A) Dwelling Units. (Bold and underlined is mine)

All 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling unit kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, or similar rooms or areas shall be protected by any of the means described in 210.12(A)(1) through (6):

So basically the 2014 NEC will require AFCIs in all homes (dwelling units) for all 15 and 20 amp 120v circuits except for bathrooms and garages.

Now here is the real kicker that has some electricians really going crazy-

210.12Arc-Fault Circuit-Interrupter Protection

(B) Branch Circuit Extensions or Modifications — Dwelling Units.

In any of the areas specified in 210.12(A), where branch-circuit wiring is modified, replaced, or extended, the branch circuit shall be protected by one of the following:

A listed combination-type AFCI located at the origin of the branch circuit

A listed outlet branch-circuit type AFCI located at the first receptacle outlet of the existing branch circuit.

Exception: AFCI protection shall not be required where the extension of the existing conductors is not more than 1.8 m (6 ft) and does not include any additional outlets or devices.


             AFCI Receptacle

This means if you modify a branch circuit,  that modification will require that the affected circuit will now have to be AFCI protected.

Update– There is a difference of opinion in regards to the following section of the code from the head and local jurisdictions. Clarification should come in the following months. As it stands it is of my opinion that when receptacles are replaced in locations that require AFCI protection that they should meet the requirements listed in Subsection (4).

NEC 406.4 General Installation Requirements

Receptacle outlets shall be located in branch circuits in accordance with Part III of Article 210. General installation requirements shall be in accordance with 406.4(A) through (F).

Section (D) Replacements.

Replacement of receptacles shall comply with 406.4(D)(1) through (D)(6), as applicable. Arc-fault circuit-interrupter type and ground-fault circuit-interrupter type receptacles shall be installed in a readily accessible location.

Sub-section (4)Arc-Fault Circuit-Interrupter Protection.

Where a receptacle outlet is supplied by a branch circuit that requires arc-fault circuit-interrupter protection as specified elsewhere in this Code, a replacement receptacle at this outlet shall be one of the following:

  • A listed outlet branch-circuit type arc-fault circuit-interrupter receptacle

  • A receptacle protected by a listed outlet branch-circuit type arc-fault circuit-interrupter type receptacle

  • A receptacle protected by a listed combination type arc-fault circuit-interrupter type circuit breaker

This requirement becomes effective January 1, 2014.


If you have not read  this article from Doug Hansen it is worth a read-  AFCIs Come of Age

Let the debate begin!!!


“If you think it’s expensive to hire a professional to do the job, wait until you hire an amateur.”

Red Adair


NCW Home Inspections, LLC  is a Licensed Washington State Home Inspection service located in Wenatchee Washington serving Chelan County, Douglas County, Kittitas County, Okanogan County and Grant County Washington and the cities of Wenatchee, Leavenworth, Cashmere, Oroville, Cle Elum, East Wenatchee, Quincy and many more…  

Your Wenatchee and Chelan Professional Real Estate, Home and Structural Pest Inspection Service

www.ncwhomeinspections.com                                               509-670-9572

Coming down the Pike-  New AFCI rules for 2014

Well there is a buzz  in the electrical world with the upcoming adoption of the 2014 NEC, (on July 1, 2014 for Washington State). The big one is in regards to AFCI (Arc Fault Circuit Interrupter) protection, and now all the areas they are to cover. (Here is an article from 2012 on why AFCI protection-  Link )

                     Arc Fault

But now the debate rages on about the new rules from the 2014 NEC in regards to these devices, their cost versus protection they provide.

2014 NEC article- 210.12Arc-Fault Circuit-Interrupter Protection

Arc-fault circuit-interrupter protection shall be provided as required in 210.12(A) (B), and (C). The arc-fault circuit interrupter shall be installed in a readily accessible location.

                      Arc Fault breaker Circuit

(A) Dwelling Units. (Bold and underlined is mine)

All 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling unit kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, or similar rooms or areas shall be protected by any of the means described in 210.12(A)(1) through (6):

So basically the 2014 NEC will require AFCIs in all homes (dwelling units) for all 15 and 20 amp 120v circuits except for bathrooms and garages.

Now here is the real kicker that has some electricians really going crazy-

210.12Arc-Fault Circuit-Interrupter Protection

(B) Branch Circuit Extensions or Modifications — Dwelling Units.

In any of the areas specified in 210.12(A), where branch-circuit wiring is modified, replaced, or extended, the branch circuit shall be protected by one of the following:

A listed combination-type AFCI located at the origin of the branch circuit

A listed outlet branch-circuit type AFCI located at the first receptacle outlet of the existing branch circuit.

Exception: AFCI protection shall not be required where the extension of the existing conductors is not more than 1.8 m (6 ft) and does not include any additional outlets or devices.


             AFCI Receptacle

This means if you modify a branch circuit,  that modification will require that the affected circuit will now have to be AFCI protected.

Update– There is a difference of opinion in regards to the following section of the code from the head and local jurisdictions. Clarification should come in the following months. As it stands it is of my opinion that when receptacles are replaced in locations that require AFCI protection that they should meet the requirements listed in Subsection (4).

NEC 406.4 General Installation Requirements

Receptacle outlets shall be located in branch circuits in accordance with Part III of Article 210. General installation requirements shall be in accordance with 406.4(A) through (F).

Section (D) Replacements.

Replacement of receptacles shall comply with 406.4(D)(1) through (D)(6), as applicable. Arc-fault circuit-interrupter type and ground-fault circuit-interrupter type receptacles shall be installed in a readily accessible location.

Sub-section (4)Arc-Fault Circuit-Interrupter Protection.

Where a receptacle outlet is supplied by a branch circuit that requires arc-fault circuit-interrupter protection as specified elsewhere in this Code, a replacement receptacle at this outlet shall be one of the following:

  • A listed outlet branch-circuit type arc-fault circuit-interrupter receptacle

  • A receptacle protected by a listed outlet branch-circuit type arc-fault circuit-interrupter type receptacle

  • A receptacle protected by a listed combination type arc-fault circuit-interrupter type circuit breaker

This requirement becomes effective January 1, 2014.


If you have not read  this article from Doug Hansen it is worth a read-  AFCIs Come of Age

Let the debate begin!!!


“If you think it’s expensive to hire a professional to do the job, wait until you hire an amateur.”

Red Adair


NCW Home Inspections, LLC  is a Licensed Washington State Home Inspection service located in Wenatchee Washington serving Chelan County, Douglas County, Kittitas County, Okanogan County and Grant County Washington and the cities of Wenatchee, Leavenworth, Cashmere, Oroville, Cle Elum, East Wenatchee, Quincy and many more…  

Your Wenatchee and Chelan Professional Real Estate, Home and Structural Pest Inspection Service

www.ncwhomeinspections.com                                               509-670-9572

Primary Sidebar

  • Menu
  • Gallery
  • Blog

Informational Pages

  • Blog
  • Foundation Certifications
  • Prices
  • Qualifications
  • Services Performed
  • Testimonials
  • Washington State Home Inspector Standards of Practice
  • What’s Inspected and Services
  • Areas Served
  • Credit card
  • City/County/State Building Codes
  • Frequently Asked Questions
  • General Home Information
  • Homeowner Maintenace Guides
  • Infrared Thermography
  • Recall Resources
  • Reference Documents
  • Inspection Agreement and Washington State Standards of Practice
  • Home and Building Inspections Wenatchee, Chelan and Surrounding Areas
    • About Me and Training Information
  • google verify

Copyright © 2025 Administrator. All rights reserved.